COMBINED FIRE EXTINGUISHING SYSTEM BASED ON THE SHOCK WAVE AND THE GAS VOLUME OF THE EXTINGUISHING AGENT

  • V. Balanyuk Lviv State University of Life Safety
Keywords: Retarder, a flame retardant, combo fighting, СО 2 , N 2 inert gases.

Abstract

The article is theoretically proved and experimentally confirmed that the combined fire-extinguishing system on the basis of the shock wave and the gas volume of the extinguishing agent have significant fire-fighting efficiency. It was established experimentally that the effect of shock waves with a frequency of 10 - 12 Hz reduces the mini mum extinguishing concentration to 4.8%. and nitrogen to 10.2% vol., with the power of WOW about 170 PA. It is proved that the action of the gas fire extinguishing substances under the influence of the WOW series has a complex synergistic effect, which is manifested in the reduction of volumetric fire extinguishing concentration of CO2 and N2 up to 50% of its original value.

Downloads

Download data is not yet available.
Published
2017-12-31
How to Cite
Balanyuk, V. (2017). COMBINED FIRE EXTINGUISHING SYSTEM BASED ON THE SHOCK WAVE AND THE GAS VOLUME OF THE EXTINGUISHING AGENT. Fire Safety, 30, 6-10. Retrieved from https://journal.ldubgd.edu.ua/index.php/PB/article/view/11